Comparison of DC breakdown voltage between multiple level test and successive discharge test methods

Conference proceedings article


Authors/Editors


Strategic Research Themes

No matching items found.


Publication Details

Author listPhontusa S., Chotigo S.

PublisherHindawi

Publication year2008

Volume number2

Start page913

End page916

Number of pages4

ISBN1424421012; 9781424421015

ISSN0146-9428

eISSN1745-4557

URLhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-52949141873&doi=10.1109%2fECTICON.2008.4600579&partnerID=40&md5=d14196735df65a84c1f977f48bd9a95c

LanguagesEnglish-Great Britain (EN-GB)


View in Web of Science | View on publisher site | View citing articles in Web of Science


Abstract

This present work was a comparison of positive DC breakdown voltage obtained by "multiple level test" and "successive discharge test" methods following IEC 60-1 (1989) of a sphere-sphere gap in air. The experiment was done under actual different atmospheric condition, temperature and absolute humidity. The ratio of absolute humidity to the air density correction factor, h/δ, was in the range of 7-13 g/m3. The diameters of the sphere were 12.5 cm and 5 cm. The results found that the breakdown voltages obtained by multiple level and successive discharge methods were very close. The average difference of breakdown voltages from these 2 methods for 12.5 cm and 5 cm sphere was 1.33% and 1.05% respectively. © 2008 IEEE.