Atmospheric factor under the negative impulse voltages on various test gaps

Conference proceedings article


Authors/Editors


Strategic Research Themes

No matching items found.


Publication Details

Author listKanchana S., Chotigo S., Pungsiri B.

PublisherHindawi

Publication year2008

Volume number2

Start page917

End page920

Number of pages4

ISBN1424421012; 9781424421015

ISSN0146-9428

eISSN1745-4557

URLhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-52949123639&doi=10.1109%2fECTICON.2008.4600580&partnerID=40&md5=fd79825dff4c343d3405b1095fcefd71

LanguagesEnglish-Great Britain (EN-GB)


View in Web of Science | View on publisher site | View citing articles in Web of Science


Abstract

This paper dealt with the effect of the atmospheric factors on various test gaps under the standard negative impulse voltage, 1.2/50μs. The atmospheric factors in this present work were relative humidity, temperature and the ratio of the absolute humidity to the air density correction factor (h/δ). Gaps used were sphere-sphere, rod-plane and rod-rod gaps. The diameter of the sphere was 12.5 cm and the length of the rod was 20 cm. The dimensions of the plane were 4*4 cm 2 copper, and 70*70 cm 2 steel. The maximum voltage used in this present work was about 230 kV. The results of the breakdown voltage (U 50) as a function of atmospheric factors were plotted. © 2008 IEEE.


Keywords

FlashoverHumidityNegative impulse voltage


Last updated on 2023-04-10 at 07:35