Microcontroller modulation for VLF high voltage generator rate 3 kV peak using DSPIC-30F2010

Conference proceedings article


Authors/Editors


Strategic Research Themes

No matching items found.


Publication Details

Author listSeesanga S., Kongnun W., Chotigo S.

PublisherHindawi

Publication year2008

Start page63

End page67

Number of pages5

ISBN9781424424054

ISSN0146-9428

eISSN1745-4557

URLhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-63049097235&doi=10.1109%2fPECON.2008.4762436&partnerID=40&md5=5b25403406075cc9f4f89ba31229ac99

LanguagesEnglish-Great Britain (EN-GB)


View in Web of Science | View on publisher site | View citing articles in Web of Science


Abstract

This paper describes a microcontroller modulation at 0.1 Hz for very low frequency (VLF) high voltage generator. This is used for testing field aged cable. This paper shows a simple type of the modulation circuit for VLF high voltage generator by microcontroller modulation with a sinusoidal signal at frequency 0.1 Hz and carrier signal at frequency 10 kHz. The unipolar pulse with modulation (PWM) technique is employed to control a single-phase inverter that produces a sinusoidal VLF high voltage of desired magnitude and frequency. This microcontroller modulation will be used to construct a sinusoidal VLF high voltage for non-destructive testing insulation of the crosslinked polyethylene (XLPE) cable. The digital signal controller (DSPIC-30F2010) is implemented to the inverter. In this paper show example to used microcontroller (DSPIC-30F2010) with VLF High Voltage Generator rate voltage output 3 kV peak. ฉ 2008 IEEE.


Keywords

Unipolar modulation technique


Last updated on 2023-29-09 at 07:35