Determination of fin pitches for maximum performance index of L-Footed spiral fin-and-tube heat exchangers
Journal article
Authors/Editors
Strategic Research Themes
No matching items found.
Publication Details
Author list: Pongsoi P., Wongwises S.
Publisher: Yildiz Technical University
Publication year: 2015
Volume number: 1
Issue number: 5
Start page: 251
End page: 262
Number of pages: 12
ISSN: 2148-7847
eISSN: 2148-7847
Languages: English-Great Britain (EN-GB)
View in Web of Science | View on publisher site | View citing articles in Web of Science
Abstract
In this study, the fin pitches of L-footed spiral finned tube heat exchangers were determined for maximimum performance index. The experiments were done at various fin pitches (fp = 2.4, 3.2, and 4.2 mm) under the range of high Reynolds numbers (5,000-15,000). The test sections had a parallel and counter cross-flow arrangement having the number of tube row of 2. The two working fluids were the ambient air and hot water. The performance indexes (ζ1, ζ2, and ζ3) were used to analyze the experimental data at different fin pitches. The results show that the optimal fin pitches for L-footed spiral finned tube heat exchangers are 2.4 and 3.2 mm.
Keywords
Optimum