Separated phase-current controls using inverter-based DGs to mitigate effects of fault current contribution from synchronous DGs on recloser-fuse

บทความในวารสาร


ผู้เขียน/บรรณาธิการ


กลุ่มสาขาการวิจัยเชิงกลยุทธ์

ไม่พบข้อมูลที่เกี่ยวข้อง


รายละเอียดสำหรับงานพิมพ์

รายชื่อผู้แต่งBoonyapakdee N., Konghirun M., Sangswang A.

ผู้เผยแพร่MDPI AG

ปีที่เผยแพร่ (ค.ศ.)2019

Volume number9

Issue number20

นอก2076-3417

eISSN2076-3417

URLhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85074161884&doi=10.3390%2fapp9204311&partnerID=40&md5=385f616609b4d7fbceff940682753d1c

ภาษาEnglish-Great Britain (EN-GB)


ดูในเว็บของวิทยาศาสตร์ | ดูบนเว็บไซต์ของสำนักพิมพ์ | บทความในเว็บของวิทยาศาสตร์


บทคัดย่อ

Synchronous distributed generators (SDGs) significantly affect recloser-fuse coordination due to the high fault current contribution. This paper proposes a separated phase-current control using inverter-based distributed generators (IBDGs) to remove the effects of fault current contributions from SDGs during unsymmetrical faults. The three-phase current produced by IBDGs is independently controlled. While the total fault current is reduced by adjusting the current phase angle in the faulty phase, the energy in the DC-link capacitor (Cdc) is delivered to the grid in order to avoid the rise of DC-link voltage (Vdc) by means of injection of the active current into the nonfaulty phase. To maintain the proper grid voltage, the voltage regulation feature is installed in the IBDGs. Moreover, current estimations programmed within the IBDGs are introduced to avoid the performance degradation of separated phase-current controls caused by phasor measurement units (PMUs). The dynamic performance of the separated phase-current controls using IBDGs was evaluated using an IEEE 34-node radial test feeder. According to the simulation results, the IBDGs could eliminate the effects of fault current contributions from the SDG without interruption since the disconnections caused by excessive Vdc were prevented. They could also regulate the grid voltage in the nonfaulty phase. ฉ 2019 by the authors.


คำสำคัญ

Recloser-fuse coordination